Two ways to read the same certified data. Switch any time; your choice is remembered on this device.
CEE 2025 Tier 1 (Split ASHP): 4,661 qualifying heat pumps
The CEE 2025 Tier 1 efficiency level for split air-source heat pumps, used by many utility rebate programs.
New to heat pump ratings? The Simple view explains them in plain words →
Consortium for Energy EfficiencyData as of updated · sources
- Share of models
- 48.4%
- Qualifying models
- 4,661
- Qualifying certifications
- 98,129
- Paths
- 2
Criteria
| Path | SEER2 | EER2 | HSPF2 | COP@5°F | Cap. 5/47 |
|---|---|---|---|---|---|
| Path A (heating-dominated) | ≥ 16 | ≥ 9.8 | ≥ 8.5 | ≥ 1.75 | ≥ 60% |
| Path B (cooling-dominated / dual fuel) | ≥ 16 | ≥ 11 | ≥ 8 | ≥ 1.75 | ≥ 45% |
Source: Consortium for Energy Efficiency
Where the thresholds fall
Every model's representative certification on each rating CEE 2025 checks, with its thresholds drawn. A model must clear every line of one path at once, on one certification, so these single-rating views show each hurdle, not the combined pass rate.
Show the data as a table
| COP@5°F range | Models |
|---|---|
| Below 1.40 | 33 |
| 1.40 to under 1.50 | 118 |
| 1.50 to under 1.60 | 83 |
| 1.60 to under 1.70 | 113 |
| 1.70 to under 1.80 | 710 |
| 1.80 to under 1.90 | 2,084 |
| 1.90 to under 2.00 | 1,248 |
| 2.00 to under 2.10 | 1,265 |
| 2.10 to under 2.20 | 597 |
| 2.20 to under 2.30 | 469 |
| 2.30 to under 2.40 | 337 |
| 2.40 to under 2.50 | 165 |
| 2.50 to under 2.60 | 113 |
| 2.60 to under 2.70 | 126 |
| 2.70 to under 2.80 | 98 |
| 2.80 to under 2.90 | 76 |
| 2.90 to under 3.00 | 40 |
| 3.00 to under 3.10 | 37 |
| 3.10 to under 3.20 | 20 |
| 3.20 and above | 23 |
| Baseline: median | 1.93 |
| Baseline: CEE 2025 1.75 | 1.75 |
Source: AHRI Directory · as of
Show the data as a table
| Cap. 5/47 range | Models |
|---|---|
| Below 30% | 11 |
| 30 to under 35% | 66 |
| 35 to under 40% | 352 |
| 40 to under 45% | 195 |
| 45 to under 50% | 286 |
| 50 to under 55% | 598 |
| 55 to under 60% | 783 |
| 60 to under 65% | 884 |
| 65 to under 70% | 798 |
| 70 to under 75% | 1,046 |
| 75 to under 80% | 472 |
| 80 to under 85% | 529 |
| 85 to under 90% | 414 |
| 90 to under 95% | 387 |
| 95 to under 100% | 270 |
| 100 to under 105% | 385 |
| 105 to under 110% | 74 |
| 110 to under 115% | 81 |
| 115 to under 120% | 27 |
| 120 to under 125% | 45 |
| 125 to under 130% | 13 |
| 130% and above | 31 |
| Baseline: median | 69% |
| Baseline: Path B 45% | 45% |
| Baseline: Path A 60% | 60% |
Source: AHRI Directory · as of
Show the data as a table
| HSPF2 range | Models |
|---|---|
| Below 6.5 | 31 |
| 6.5 to under 6.8 | 691 |
| 6.8 to under 7.0 | 67 |
| 7.0 to under 7.3 | 239 |
| 7.3 to under 7.5 | 65 |
| 7.5 to under 7.8 | 1,051 |
| 7.8 to under 8.0 | 534 |
| 8.0 to under 8.3 | 813 |
| 8.3 to under 8.5 | 123 |
| 8.5 to under 8.8 | 1,436 |
| 8.8 to under 9.0 | 268 |
| 9.0 to under 9.3 | 944 |
| 9.3 to under 9.5 | 361 |
| 9.5 to under 9.8 | 692 |
| 9.8 to under 10.0 | 272 |
| 10.0 to under 10.3 | 623 |
| 10.3 to under 10.5 | 171 |
| 10.5 to under 10.8 | 303 |
| 10.8 to under 11.0 | 79 |
| 11.0 to under 11.3 | 175 |
| 11.3 to under 11.5 | 85 |
| 11.5 to under 11.8 | 116 |
| 11.8 to under 12.0 | 10 |
| 12.0 to under 12.3 | 32 |
| 12.3 to under 12.5 | 17 |
| 12.5 to under 12.8 | 9 |
| 12.8 to under 13.0 | 4 |
| 13.0 to under 13.3 | 0 |
| 13.3 to under 13.5 | 4 |
| 13.5 and above | 45 |
| Baseline: median | 8.6 |
| Baseline: Path B 8 | 8.0 |
| Baseline: Path A 8.5 | 8.5 |
Source: AHRI Directory · as of
Show the data as a table
| SEER2 range | Models |
|---|---|
| Below 13.0 | 43 |
| 13.0 to under 13.5 | 658 |
| 13.5 to under 14.0 | 22 |
| 14.0 to under 14.5 | 570 |
| 14.5 to under 15.0 | 317 |
| 15.0 to under 15.5 | 986 |
| 15.5 to under 16.0 | 347 |
| 16.0 to under 16.5 | 714 |
| 16.5 to under 17.0 | 306 |
| 17.0 to under 17.5 | 523 |
| 17.5 to under 18.0 | 319 |
| 18.0 to under 18.5 | 370 |
| 18.5 to under 19.0 | 277 |
| 19.0 to under 19.5 | 590 |
| 19.5 to under 20.0 | 163 |
| 20.0 to under 20.5 | 480 |
| 20.5 to under 21.0 | 259 |
| 21.0 to under 21.5 | 534 |
| 21.5 to under 22.0 | 326 |
| 22.0 to under 22.5 | 337 |
| 22.5 to under 23.0 | 182 |
| 23.0 to under 23.5 | 295 |
| 23.5 to under 24.0 | 167 |
| 24.0 to under 24.5 | 106 |
| 24.5 to under 25.0 | 55 |
| 25.0 to under 25.5 | 33 |
| 25.5 to under 26.0 | 56 |
| 26.0 to under 26.5 | 49 |
| 26.5 to under 27.0 | 37 |
| 27.0 to under 27.5 | 31 |
| 27.5 to under 28.0 | 26 |
| 28.0 to under 28.5 | 48 |
| 28.5 and above | 34 |
| Baseline: median | 17.5 |
| Baseline: CEE 2025 16 | 16.0 |
Source: AHRI Directory · as of
Show the data as a table
| EER2 range | Models |
|---|---|
| Below 8.0 | 4 |
| 8.0 to under 8.5 | 244 |
| 8.5 to under 9.0 | 584 |
| 9.0 to under 9.5 | 515 |
| 9.5 to under 10.0 | 387 |
| 10.0 to under 10.5 | 900 |
| 10.5 to under 11.0 | 1,155 |
| 11.0 to under 11.5 | 964 |
| 11.5 to under 12.0 | 1,095 |
| 12.0 to under 12.5 | 908 |
| 12.5 to under 13.0 | 1,265 |
| 13.0 to under 13.5 | 568 |
| 13.5 to under 14.0 | 228 |
| 14.0 to under 14.5 | 126 |
| 14.5 to under 15.0 | 44 |
| 15.0 to under 15.5 | 95 |
| 15.5 to under 16.0 | 77 |
| 16.0 to under 16.5 | 68 |
| 16.5 and above | 33 |
| Baseline: median | 11.3 |
| Baseline: Path A 9.8 | 9.8 |
| Baseline: Path B 11 | 11.0 |
Source: AHRI Directory · as of
Qualification by size
- Up to 1.5 tons69.5% · 2,175 of 3,129
- 2 tons56.5% · 812 of 1,436
- 2.5–3 tons41.4% · 1,072 of 2,587
- 3.5–4.5 tons25.5% · 545 of 2,136
- 5 tons and up16.3% · 57 of 349
Show the data as a table
| Group | Qualifying share |
|---|---|
| Up to 1.5 tons | 69.5% · 2,175 of 3,129 |
| 2 tons | 56.5% · 812 of 1,436 |
| 2.5–3 tons | 41.4% · 1,072 of 2,587 |
| 3.5–4.5 tons | 25.5% · 545 of 2,136 |
| 5 tons and up | 16.3% · 57 of 349 |
Qualification by duct type
| Type | Share | Qualifying / total |
|---|---|---|
| Ducted | 25.8% | 1,175 / 4,546 |
| Non-ducted | 60.4% | 1,955 / 3,236 |
| Ducted and non-ducted | 82.5% | 1,531 / 1,855 |
Manufacturers with the most qualifying models
Among manufacturers with at least 5 models.
| Manufacturer | Qualifying | Share of its models |
|---|---|---|
| Mitsubishi Electric | 253 of 373 | 67.8% |
| Midea | 242 of 402 | 60.2% |
| Gree | 233 of 395 | 59% |
| Carrier | 200 of 701 | 28.5% |
| Lennox | 144 of 313 | 46% |
| Rheem | 117 of 291 | 40.2% |
| Hisense | 103 of 159 | 64.8% |
| Daikin | 99 of 367 | 27% |
| Trane | 97 of 309 | 31.4% |
| ACIQ | 66 of 161 | 41% |
Qualifying models
Sorted by manufacturer and model. Use Explore for other sorts and filters.
| # · Outdoor model | Manufacturer | Size · type | COP@5°F | Cap. 5/47 | HSPF2 | SEER2 | Meets | Combos | AHRI ref. |
|---|---|---|---|---|---|---|---|---|---|
| 42514A6C7036A3AMERICAN STANDARD · GOLD17with ducted air handler 4PX*BU36BS3+P0V0B000M40SC | Trane | 3 tons35,800 Btu/h · Ducted | 2.00 | 49% | 7.5 | 16.5 | CEE 25 | 15 | 213867260 |
| 42524A6C7048A3AMERICAN STANDARD · GOLD17with ducted air handler 4PX*CU60BS3+P0V0C000M50SC | Trane | 4 tons48,000 Btu/h · Ducted | 3.60 | 101% | 8.1 | 17.0 | CEE 25CEE 26Xcel | 24 | 213867303 |
| 42534A6C7048A4AMERICAN STANDARD · GOLD17with ducted air handler 4PX*CU60BS3+P0V0C000M50SC | Trane | 4 tons48,000 Btu/h · Ducted | 3.60 | 101% | 8.1 | 17.0 | CEE 25CEE 26Xcel | 24 | 213867330 |
| 42544A6H5024N1AMERICAN STANDARDwith indoor coil D(A,C,E)36C34+TDR and furnace *UD2B060ACV3 | Trane | 2 tons23,600 Btu/h · Ducted | 2.62 | 67% | 7.5 | 15.2 | CEE 25CEE 26Xcel | 1,216 | 212913864 |
| 42554A6H5042N1AMERICAN STANDARDwith ducted air handler AE(D,N,U)+CM48B44+TDR | Trane | 3 tons37,400 Btu/h · Ducted | 2.74 | 58% | 7.9 | 14.7 | CEE 25 | 1,975 | 214638520 |
| 42564A6H5048N1AMERICAN STANDARDwith ducted air handler AE(D,N,U)+DM59A44+TDR | Trane | 3.5 tons42,500 Btu/h · Ducted | 2.57 | 63% | 7.7 | 15.1 | CEE 25Xcel | 1,651 | 214384670 |
| 42574A6H6024N1AMERICAN STANDARDwith indoor coil D(A,C,E)36C34+TDR and furnace *UHMC100ACV4 | Trane | 2 tons25,600 Btu/h · Ducted | 2.62 | 60% | 7.8 | 16.0 | CEE 25CEE 26 | 936 | 212913826 |
| 42584A6H6036N1AMERICAN STANDARDwith ducted air handler L(E,G)M48A4 | Trane | 3 tons36,000 Btu/h · Ducted | 2.60 | 63% | 7.5 | 16.3 | CEE 25CEE 26 | 1,341 | 213295994 |
| 42594A6H6048N1AMERICAN STANDARDwith indoor coil D(A,C,E)48C34+TDR and furnace *UD2C100ACV5 | Trane | 4 tons46,000 Btu/h · Ducted | 2.59 | 63% | 7.8 | 16.0 | CEE 25CEE 26 | 1,573 | 212913824 |
| 42604A6H7024A1AMERICAN STANDARD · GOLD 17 / PLATINUM XMwith indoor coil 4PX*BU48BS3 and furnace *UHMB080CCV3 | Trane | 2 tons25,600 Btu/h · Ducted | 2.10 | 46% | 8.1 | 16.0 | CEE 25 | 154 | 213915489 |
| 42614A6H7048A1AMERICAN STANDARDwith ducted air handler F,PE*TT7960 | Trane | 4 tons45,000 Btu/h · Ducted | 2.10 | 51% | 8.1 | 16.0 | CEE 25CEE 26 | 265 | 212349223 |
| 42624A6L5024N1AMERICAN STANDARDwith ducted air handler TEM6A0C36H31+TDR | Trane | 2 tons25,600 Btu/h · Ducted | 2.28 | 55% | 8.1 | 16.0 | CEE 25CEE 26 | 1,088 | 210793122 |
| 42634A6L5030N1AMERICAN STANDARDwith ducted air handler TEM6A0C36H31+TDR | Trane | 2.5 tons30,400 Btu/h · Ducted | 2.28 | 51% | 8.1 | 16.0 | CEE 25CEE 26 | 1,636 | 210793667 |
| 42644A6L5036N1AMERICAN STANDARDwith ducted air handler TEM8A0C48V41+TDR | Trane | 3 tons36,600 Btu/h · Ducted | 2.10 | 47% | 8.1 | 16.0 | CEE 25 | 1,637 | 210791257 |
| 42654A6L9024A1AMERICAN STANDARDwith indoor coil 4PX*BU42BS3 and furnace S9V2B060U3PSB+RP | Trane | 2 tons23,800 Btu/h · Ducted | 2.52 | 53% | 8.7 | 17.5 | CEE 25CEE 26 | 204 | 201922873 |
| 42664A6L9036A1AMERICAN STANDARDwith indoor coil 4PX*CU48BS3 and furnace S9V2C100U4PSB+RP | Trane | 3 tons36,600 Btu/h · Ducted | 2.47 | 54% | 8.7 | 17.5 | CEE 25CEE 26 | 732 | 201922405 |
| 42674A6L9048A1AMERICAN STANDARD · Platinum 19with indoor coil TEM8A0C48V41+TDR and furnace N/A | Trane | 4 tons48,500 Btu/h · Ducted | 2.38 | 58% | 9.0 | 19.0 | CEE 25CEE 26 | 561 | 201922736 |
| 42684A6L9060A1AMERICAN STANDARD · Platinum 19with indoor coil 4TXCD010DS3 and furnace S9V2D120U5PSB+RP | Trane | 5 tons58,500 Btu/h · Ducted | 2.40 | 58% | 8.7 | 19.0 | CEE 25CEE 26 | 401 | 201922829 |
| 42694A6V0024A1AMERICAN STANDARDwith ducted air handler D(A,C,E)36A44+JMET08BS2N1+TDR | Trane | 2 tons22,000 Btu/h · Ducted | 2.43 | 82% | 8.3 | 18.9 | CEE 25CEE 26Xcel | 2 | 213295992 |
| 42704A6V0X24A1AMERICAN STANDARDwith ducted air handler D(A,C,E)36A44+JMET12BS2N1+TDR | Trane | 2 tons22,000 Btu/h · Ducted | 2.42 | 80% | 8.3 | 18.9 | CEE 25CEE 26Xcel | 95 | 213295993 |
| 42714A6V0X36A1AMERICAN STANDARDwith indoor coil 4PX*CU48BS3 and furnace S9V2C100U4PSB+RP | Trane | 3 tons35,600 Btu/h · Ducted | 1.94 | 63% | 8.7 | 20.5 | CEE 25CEE 26XcelES CC | 348 | 207590099 |
| 42724A6V0X48A1AMERICAN STANDARDwith indoor coil 4TXCC009DS3 and furnace P0V0C000M50SA+RP | Trane | 4 tons47,500 Btu/h · Ducted | 1.94 | 70% | — | — | CEE 25CEE 26Xcel | 489 | 207590311 |
| 42734A6V0X60A1AMERICAN STANDARD · XV20Iwith indoor coil TEM8A0D48V41+TDR and furnace N/A | Trane | 4.5 tons52,000 Btu/h · Ducted | 1.86 | 72% | 8.7 | 18.5 | CEE 25CEE 26XcelES CC | 130 | 207590063 |
| 42744A6V7X24A1AMERICAN STANDARD · PLATINUM 17with ducted air handler TAMXB0B30V31 | Trane | 2 tons23,800 Btu/h · Ducted | 1.92 | 71% | 8.5 | 17.1 | CEE 25CEE 26Xcel | 115 | 212391564 |
| 42754A6V7X36A1AMERICAN STANDARD · PLATINUM 17with ducted air handler TEM8A0C36V31+TDR+LRP | Trane | 3 tons34,800 Btu/h · Ducted | 1.90 | 63% | 8.5 | 17.1 | CEE 25CEE 26Xcel | 351 | 214671725 |