CEE 2025 Tier 1 (Split ASHP): 4,665 qualifying heat pumps
The CEE 2025 Tier 1 efficiency level for split air-source heat pumps, used by many utility rebate programs.
New to heat pump ratings? The Simple view explains them in plain words →
Consortium for Energy EfficiencyData as of updated · sources
- Share of models
- 48.1%
- Qualifying models
- 4,665
- Qualifying certifications
- 98,137
- Paths
- 2
Criteria
| Path | SEER2 | EER2 | HSPF2 | COP@5°F | Cap. 5/47 |
|---|---|---|---|---|---|
| Path A (heating-dominated) | ≥ 16 | ≥ 9.8 | ≥ 8.5 | ≥ 1.75 | ≥ 60% |
| Path B (cooling-dominated / dual fuel) | ≥ 16 | ≥ 11 | ≥ 8 | ≥ 1.75 | ≥ 45% |
Source: Consortium for Energy Efficiency
Where the thresholds fall
Every model's representative certification on each rating CEE 2025 checks, with its thresholds drawn. A model must clear every line of one path at once, on one certification, so these single-rating views show each hurdle, not the combined pass rate.
Show the data as a table
| COP@5°F range | Models |
|---|---|
| Below 1.40 | 37 |
| 1.40 to under 1.50 | 123 |
| 1.50 to under 1.60 | 87 |
| 1.60 to under 1.70 | 115 |
| 1.70 to under 1.80 | 716 |
| 1.80 to under 1.90 | 2,089 |
| 1.90 to under 2.00 | 1,247 |
| 2.00 to under 2.10 | 1,265 |
| 2.10 to under 2.20 | 607 |
| 2.20 to under 2.30 | 477 |
| 2.30 to under 2.40 | 345 |
| 2.40 to under 2.50 | 165 |
| 2.50 to under 2.60 | 113 |
| 2.60 to under 2.70 | 126 |
| 2.70 to under 2.80 | 98 |
| 2.80 to under 2.90 | 76 |
| 2.90 to under 3.00 | 40 |
| 3.00 to under 3.10 | 37 |
| 3.10 to under 3.20 | 20 |
| 3.20 and above | 23 |
| Baseline: median | 1.93 |
| Baseline: CEE 2025 1.75 | 1.75 |
Source: AHRI Directory · as of
Show the data as a table
| Cap. 5/47 range | Models |
|---|---|
| Below 30% | 11 |
| 30 to under 35% | 66 |
| 35 to under 40% | 366 |
| 40 to under 45% | 200 |
| 45 to under 50% | 286 |
| 50 to under 55% | 599 |
| 55 to under 60% | 783 |
| 60 to under 65% | 885 |
| 65 to under 70% | 799 |
| 70 to under 75% | 1,049 |
| 75 to under 80% | 488 |
| 80 to under 85% | 537 |
| 85 to under 90% | 414 |
| 90 to under 95% | 387 |
| 95 to under 100% | 270 |
| 100 to under 105% | 387 |
| 105 to under 110% | 74 |
| 110 to under 115% | 81 |
| 115 to under 120% | 27 |
| 120 to under 125% | 45 |
| 125 to under 130% | 13 |
| 130% and above | 31 |
| Baseline: median | 69% |
| Baseline: Path B 45% | 45% |
| Baseline: Path A 60% | 60% |
Source: AHRI Directory · as of
Show the data as a table
| HSPF2 range | Models |
|---|---|
| Below 6.5 | 31 |
| 6.5 to under 6.8 | 711 |
| 6.8 to under 7.0 | 67 |
| 7.0 to under 7.3 | 263 |
| 7.3 to under 7.5 | 67 |
| 7.5 to under 7.8 | 1,051 |
| 7.8 to under 8.0 | 534 |
| 8.0 to under 8.3 | 813 |
| 8.3 to under 8.5 | 123 |
| 8.5 to under 8.8 | 1,436 |
| 8.8 to under 9.0 | 268 |
| 9.0 to under 9.3 | 947 |
| 9.3 to under 9.5 | 363 |
| 9.5 to under 9.8 | 693 |
| 9.8 to under 10.0 | 272 |
| 10.0 to under 10.3 | 623 |
| 10.3 to under 10.5 | 171 |
| 10.5 to under 10.8 | 303 |
| 10.8 to under 11.0 | 79 |
| 11.0 to under 11.3 | 175 |
| 11.3 to under 11.5 | 85 |
| 11.5 to under 11.8 | 116 |
| 11.8 to under 12.0 | 10 |
| 12.0 to under 12.3 | 32 |
| 12.3 to under 12.5 | 17 |
| 12.5 to under 12.8 | 9 |
| 12.8 to under 13.0 | 4 |
| 13.0 to under 13.3 | 0 |
| 13.3 to under 13.5 | 4 |
| 13.5 and above | 45 |
| Baseline: median | 8.6 |
| Baseline: Path B 8 | 8.0 |
| Baseline: Path A 8.5 | 8.5 |
Source: AHRI Directory · as of
Show the data as a table
| SEER2 range | Models |
|---|---|
| Below 13.0 | 43 |
| 13.0 to under 13.5 | 678 |
| 13.5 to under 14.0 | 22 |
| 14.0 to under 14.5 | 570 |
| 14.5 to under 15.0 | 317 |
| 15.0 to under 15.5 | 1,004 |
| 15.5 to under 16.0 | 355 |
| 16.0 to under 16.5 | 714 |
| 16.5 to under 17.0 | 306 |
| 17.0 to under 17.5 | 523 |
| 17.5 to under 18.0 | 319 |
| 18.0 to under 18.5 | 371 |
| 18.5 to under 19.0 | 279 |
| 19.0 to under 19.5 | 593 |
| 19.5 to under 20.0 | 163 |
| 20.0 to under 20.5 | 480 |
| 20.5 to under 21.0 | 259 |
| 21.0 to under 21.5 | 534 |
| 21.5 to under 22.0 | 326 |
| 22.0 to under 22.5 | 337 |
| 22.5 to under 23.0 | 182 |
| 23.0 to under 23.5 | 295 |
| 23.5 to under 24.0 | 167 |
| 24.0 to under 24.5 | 106 |
| 24.5 to under 25.0 | 55 |
| 25.0 to under 25.5 | 33 |
| 25.5 to under 26.0 | 56 |
| 26.0 to under 26.5 | 49 |
| 26.5 to under 27.0 | 37 |
| 27.0 to under 27.5 | 31 |
| 27.5 to under 28.0 | 26 |
| 28.0 to under 28.5 | 48 |
| 28.5 and above | 34 |
| Baseline: median | 17.5 |
| Baseline: CEE 2025 16 | 16.0 |
Source: AHRI Directory · as of
Show the data as a table
| EER2 range | Models |
|---|---|
| Below 8.0 | 4 |
| 8.0 to under 8.5 | 244 |
| 8.5 to under 9.0 | 584 |
| 9.0 to under 9.5 | 515 |
| 9.5 to under 10.0 | 388 |
| 10.0 to under 10.5 | 900 |
| 10.5 to under 11.0 | 1,175 |
| 11.0 to under 11.5 | 983 |
| 11.5 to under 12.0 | 1,096 |
| 12.0 to under 12.5 | 918 |
| 12.5 to under 13.0 | 1,266 |
| 13.0 to under 13.5 | 568 |
| 13.5 to under 14.0 | 228 |
| 14.0 to under 14.5 | 126 |
| 14.5 to under 15.0 | 44 |
| 15.0 to under 15.5 | 95 |
| 15.5 to under 16.0 | 77 |
| 16.0 to under 16.5 | 68 |
| 16.5 and above | 33 |
| Baseline: median | 11.3 |
| Baseline: Path A 9.8 | 9.8 |
| Baseline: Path B 11 | 11.0 |
Source: AHRI Directory · as of
Qualification by size
- Up to 1.5 tons69.5% · 2,175 of 3,130
- 2 tons56.5% · 813 of 1,440
- 2.5–3 tons41.2% · 1,074 of 2,606
- 3.5–4.5 tons25.3% · 546 of 2,161
- 5 tons and up15.9% · 57 of 358
Show the data as a table
| Group | Qualifying share |
|---|---|
| Up to 1.5 tons | 69.5% · 2,175 of 3,130 |
| 2 tons | 56.5% · 813 of 1,440 |
| 2.5–3 tons | 41.2% · 1,074 of 2,606 |
| 3.5–4.5 tons | 25.3% · 546 of 2,161 |
| 5 tons and up | 15.9% · 57 of 358 |
Qualification by duct type
| Type | Share | Qualifying / total |
|---|---|---|
| Ducted | 25.5% | 1,174 / 4,597 |
| Non-ducted | 60.4% | 1,955 / 3,236 |
| Ducted and non-ducted | 82.5% | 1,536 / 1,862 |
Manufacturers with the most qualifying models
Among manufacturers with at least 5 models.
| Manufacturer | Qualifying | Share of its models |
|---|---|---|
| Mitsubishi Electric | 253 of 373 | 67.8% |
| Midea | 242 of 402 | 60.2% |
| Gree | 233 of 395 | 59% |
| Carrier | 200 of 701 | 28.5% |
| Lennox | 148 of 371 | 39.9% |
| Rheem | 117 of 291 | 40.2% |
| Hisense | 103 of 159 | 64.8% |
| Daikin | 99 of 367 | 27% |
| Trane | 97 of 309 | 31.4% |
| ACIQ | 66 of 161 | 41% |
Qualifying models
Sorted by manufacturer and model. Use Explore for other sorts and filters.
| # · Outdoor model | Manufacturer | Size · type | COP@5°F | Cap. 5/47 | HSPF2 | SEER2 | Meets | Combos | AHRI ref. |
|---|---|---|---|---|---|---|---|---|---|
| 1726NS22H36MA4-**AGEwith indoor coil D(A,C,E)36D44+TDR and furnace NF80D090T4B- | GE Appliances | 3 tons34,200 Btu/h · Ducted | 2.83 | 65% | 9.3 | 19.0 | CEE 25CEE 26 | 423 | 213884499 |
| 1727NS22H48MA4-**AGEwith indoor coil D(A,C,E)48D44+TDR and furnace NF80U110T5C | GE Appliances | 4 tons46,000 Btu/h · Ducted | 2.37 | 63% | 8.5 | 18.5 | CEE 25CEE 26 | 150 | 213884753 |
| 1728NS22H60MA4-**AGEwith indoor coil D(A,C,E)60B34+TDR and furnace NF96U135V5D | GE Appliances | 4 tons49,500 Btu/h · Ducted | 2.33 | 68% | 7.9 | 17.5 | CEE 25CEE 26 | 122 | 213884829 |
| 1729GNS-12HCH22TO1GENERALLUX STAR · E-starwith ductless indoor unit GNS-12HCH22TI1 | GENERALLUX STAR | 1 ton12,000 Btu/h · Non-ducted | 1.85 | 80% | 9.5 | 21.0 | CEE 25CEE 26Xcel | 1 | 213617766 |
| 1730GNS-12HCH23TO2GENERALLUX STAR · HYPER HEATwith ductless indoor unit GNS-12HCH23TI2 | GENERALLUX STAR | 1 ton12,000 Btu/h · Non-ducted | 1.89 | 83% | 9.5 | 23.5 | CEE 25CEE 26Xcel | 1 | 213617768 |
| 1731GNS-18HCH21TO2GENERALLUX STAR · HYPER HEATwith ductless indoor unit GNS-18HCH21TI2 | GENERALLUX STAR | 1.5 tons18,000 Btu/h · Non-ducted | 1.80 | 86% | 9.5 | 20.5 | CEE 25CEE 26Xcel | 1 | 213617769 |
| 1732GNS-18HCH23TO1GENERALLUX STAR · E-starwith ductless indoor unit GNS-18HCH23TI1 | GENERALLUX STAR | 1.5 tons18,000 Btu/h · Non-ducted | 1.87 | 77% | 8.6 | 22.5 | CEE 25CEE 26Xcel | 1 | 213617767 |
| 1733GA-09HP115V/OGenie Aire · GA serieswith ductless indoor unit GA-09HP115V/I | Genie Aire | 1 ton9,000 Btu/h · Non-ducted | 2.16 | 70% | 9.1 | 21.5 | CEE 25CEE 26XcelES CC | 1 | 212674037 |
| 1734GA-12HP230V/OGenie Airewith ductless indoor unit GA-12HP230V/I | Genie Aire | 1 ton12,000 Btu/h · Non-ducted | 1.79 | 67% | 9.2 | 21.4 | CEE 25CEE 26 | 1 | 212674039 |
| 1735GA-18HP230V/OGenie Aire · GA serieswith ductless indoor unit GA-18HP230V/I | Genie Aire | 1.5 tons18,000 Btu/h · Non-ducted | 2.07 | 62% | 8.7 | 19.5 | CEE 25CEE 26 | 1 | 212674040 |
| 1736ASZC702410A*GOETTLwith ducted air handler AMVT30BP1400A | GOETTL | 2 tons23,800 Btu/h · Ducted | 2.00 | 47% | 8.2 | 17.2 | CEE 25 | 29 | 212289321 |
| 1737ASZC703610A*GOETTLwith ducted air handler AMVT42CP1400A | GOETTL | 3 tons34,800 Btu/h · Ducted | 2.00 | 50% | 8.1 | 17.2 | CEE 25CEE 26 | 37 | 212289350 |
| 1738ASZC704810A*GOETTLwith ducted air handler AMVT60DP1400A | GOETTL | 4 tons46,500 Btu/h · Ducted | 2.00 | 45% | 8.2 | 17.2 | CEE 25 | 31 | 212289387 |
| 1739ASZS601810A*GOETTLwith ducted air handler AHVE24BP1400A | GOETTL | 1.5 tons16,600 Btu/h · Ducted | 2.10 | 75% | 8.5 | 17.5 | CEE 25CEE 26Xcel | 31 | 212290949 |
| 1740ASZV902410A*GOETTLwith ducted air handler AMVE24BP1400A | GOETTL | 2 tons22,400 Btu/h · Ducted | 2.20 | 56% | 8.2 | 20.5 | CEE 25CEE 26 | 40 | 212362505 |
| 1741ASZV903610A*GOETTLwith ducted air handler AMVE36CP1400A | GOETTL | 3 tons33,600 Btu/h · Ducted | 1.80 | 72% | 8.2 | 18.5 | CEE 25CEE 26Xcel | 90 | 212362546 |
| 1742ASZV904810A*GOETTLwith ducted air handler AMVE48DP1400A | GOETTL | 3.5 tons44,000 Btu/h · Ducted | 1.80 | 56% | 8.2 | 20.0 | CEE 25CEE 26 | 53 | 212362636 |
| 1743GSZC702410A*GOETTLwith ducted air handler AMVT30BP1400A | GOETTL | 2 tons23,800 Btu/h · Ducted | 2.00 | 47% | 8.2 | 17.2 | CEE 25 | 29 | 212291588 |
| 1744GSZC703610A*GOETTLwith ducted air handler AMVT42CP1400A | GOETTL | 3 tons34,800 Btu/h · Ducted | 2.00 | 50% | 8.1 | 17.2 | CEE 25CEE 26 | 37 | 212291617 |
| 1745GSZC704810A*GOETTLwith ducted air handler AMVT60DP1400A | GOETTL | 4 tons46,500 Btu/h · Ducted | 2.00 | 45% | 8.2 | 17.2 | CEE 25 | 31 | 212291654 |
| 1746GSZV902410A*GOETTLwith ducted air handler AMVE24BP1400A | GOETTL | 2 tons22,400 Btu/h · Ducted | 2.20 | 56% | 8.2 | 20.5 | CEE 25CEE 26 | 40 | 212362715 |
| 1747GSZV903610A*GOETTLwith ducted air handler AMVE36CP1400A | GOETTL | 3 tons33,600 Btu/h · Ducted | 1.80 | 72% | 8.2 | 18.5 | CEE 25CEE 26Xcel | 90 | 212362756 |
| 1748GSZV904810A*GOETTLwith ducted air handler AMVE48DP1400A | GOETTL | 3.5 tons44,000 Btu/h · Ducted | 1.80 | 56% | 8.2 | 20.0 | CEE 25CEE 26 | 53 | 212362846 |
| 17493VIR12HP115V1AOGREE · Vireo GEN2with ductless indoor unit 3VIR12HP115V1AH | Gree | 1 ton12,100 Btu/h · Non-ducted | 1.84 | 74% | 9.0 | 25.0 | CEE 25CEE 26Xcel | 1 | 206839103 |
| 17503VIR12HP115V1BOGREE · Vireo GEN3with ductless indoor unit 3VIR12HP115V1AH | Gree | 1 ton12,000 Btu/h · Non-ducted | 1.86 | 73% | 9.0 | 24.0 | CEE 25CEE 26XcelES CC | 2 | 210278971 |