Xcel Energy Colorado cold-climate ASHP (2025): 3,656 qualifying heat pumps
The efficiency thresholds Xcel Energy Colorado uses for its cold-climate air-source heat pump rebate.
New to heat pump ratings? The Simple view explains them in plain words →
Xcel EnergyData as of updated · sources
- Share of models
- 37.7%
- Qualifying models
- 3,656
- Qualifying certifications
- 83,200
- Paths
- 2
Criteria
| Path | SEER2 | EER2 | COP@5°F | Cap. 5/47 |
|---|---|---|---|---|
| DuctedDucted equipment only | ≥ 15.2 | ≥ 10 | ≥ 1.75 | ≥ 70% |
| Non-ductedNon-ducted equipment only | ≥ 16 | ≥ 9 | ≥ 1.75 | ≥ 70% |
Where the thresholds fall
Every model's representative certification on each rating Xcel CC checks, with its thresholds drawn. A model must clear every line of one path at once, on one certification, so these single-rating views show each hurdle, not the combined pass rate.
Show the data as a table
| COP@5°F range | Models |
|---|---|
| Below 1.40 | 37 |
| 1.40 to under 1.50 | 123 |
| 1.50 to under 1.60 | 87 |
| 1.60 to under 1.70 | 115 |
| 1.70 to under 1.80 | 716 |
| 1.80 to under 1.90 | 2,089 |
| 1.90 to under 2.00 | 1,248 |
| 2.00 to under 2.10 | 1,265 |
| 2.10 to under 2.20 | 607 |
| 2.20 to under 2.30 | 477 |
| 2.30 to under 2.40 | 345 |
| 2.40 to under 2.50 | 165 |
| 2.50 to under 2.60 | 113 |
| 2.60 to under 2.70 | 126 |
| 2.70 to under 2.80 | 98 |
| 2.80 to under 2.90 | 76 |
| 2.90 to under 3.00 | 40 |
| 3.00 to under 3.10 | 37 |
| 3.10 to under 3.20 | 20 |
| 3.20 and above | 23 |
| Baseline: median | 1.93 |
| Baseline: Xcel 1.75 | 1.75 |
Source: AHRI Directory · as of
Show the data as a table
| Cap. 5/47 range | Models |
|---|---|
| Below 30% | 11 |
| 30 to under 35% | 66 |
| 35 to under 40% | 366 |
| 40 to under 45% | 200 |
| 45 to under 50% | 286 |
| 50 to under 55% | 599 |
| 55 to under 60% | 783 |
| 60 to under 65% | 886 |
| 65 to under 70% | 799 |
| 70 to under 75% | 1,049 |
| 75 to under 80% | 488 |
| 80 to under 85% | 537 |
| 85 to under 90% | 414 |
| 90 to under 95% | 387 |
| 95 to under 100% | 270 |
| 100 to under 105% | 387 |
| 105 to under 110% | 74 |
| 110 to under 115% | 81 |
| 115 to under 120% | 27 |
| 120 to under 125% | 45 |
| 125 to under 130% | 13 |
| 130% and above | 31 |
| Baseline: median | 69% |
| Baseline: Xcel 70% | 70% |
Source: AHRI Directory · as of
Show the data as a table
| SEER2 range | Models |
|---|---|
| Below 13.0 | 43 |
| 13.0 to under 13.5 | 678 |
| 13.5 to under 14.0 | 22 |
| 14.0 to under 14.5 | 570 |
| 14.5 to under 15.0 | 318 |
| 15.0 to under 15.5 | 1,004 |
| 15.5 to under 16.0 | 355 |
| 16.0 to under 16.5 | 714 |
| 16.5 to under 17.0 | 306 |
| 17.0 to under 17.5 | 523 |
| 17.5 to under 18.0 | 319 |
| 18.0 to under 18.5 | 371 |
| 18.5 to under 19.0 | 279 |
| 19.0 to under 19.5 | 593 |
| 19.5 to under 20.0 | 163 |
| 20.0 to under 20.5 | 480 |
| 20.5 to under 21.0 | 259 |
| 21.0 to under 21.5 | 534 |
| 21.5 to under 22.0 | 326 |
| 22.0 to under 22.5 | 337 |
| 22.5 to under 23.0 | 182 |
| 23.0 to under 23.5 | 295 |
| 23.5 to under 24.0 | 167 |
| 24.0 to under 24.5 | 106 |
| 24.5 to under 25.0 | 55 |
| 25.0 to under 25.5 | 33 |
| 25.5 to under 26.0 | 56 |
| 26.0 to under 26.5 | 49 |
| 26.5 to under 27.0 | 37 |
| 27.0 to under 27.5 | 31 |
| 27.5 to under 28.0 | 26 |
| 28.0 to under 28.5 | 48 |
| 28.5 and above | 34 |
| Baseline: median | 17.5 |
| Baseline: Ducted 15.2 | 15.2 |
| Baseline: Non-ducted 16 | 16.0 |
Source: AHRI Directory · as of
Show the data as a table
| EER2 range | Models |
|---|---|
| Below 8.0 | 4 |
| 8.0 to under 8.5 | 244 |
| 8.5 to under 9.0 | 584 |
| 9.0 to under 9.5 | 515 |
| 9.5 to under 10.0 | 388 |
| 10.0 to under 10.5 | 901 |
| 10.5 to under 11.0 | 1,175 |
| 11.0 to under 11.5 | 983 |
| 11.5 to under 12.0 | 1,096 |
| 12.0 to under 12.5 | 918 |
| 12.5 to under 13.0 | 1,266 |
| 13.0 to under 13.5 | 568 |
| 13.5 to under 14.0 | 228 |
| 14.0 to under 14.5 | 126 |
| 14.5 to under 15.0 | 44 |
| 15.0 to under 15.5 | 95 |
| 15.5 to under 16.0 | 77 |
| 16.0 to under 16.5 | 68 |
| 16.5 and above | 33 |
| Baseline: median | 11.3 |
| Baseline: Non-ducted 9 | 9.0 |
| Baseline: Ducted 10 | 10.0 |
Source: AHRI Directory · as of
Qualification by size
- Up to 1.5 tons54.1% · 1,693 of 3,130
- 2 tons46.4% · 668 of 1,440
- 2.5–3 tons31.5% · 820 of 2,606
- 3.5–4.5 tons20.7% · 447 of 2,162
- 5 tons and up7.8% · 28 of 358
Show the data as a table
| Group | Qualifying share |
|---|---|
| Up to 1.5 tons | 54.1% · 1,693 of 3,130 |
| 2 tons | 46.4% · 668 of 1,440 |
| 2.5–3 tons | 31.5% · 820 of 2,606 |
| 3.5–4.5 tons | 20.7% · 447 of 2,162 |
| 5 tons and up | 7.8% · 28 of 358 |
Qualification by duct type
| Type | Share | Qualifying / total |
|---|---|---|
| Ducted | 20.9% | 959 / 4,598 |
| Non-ducted | 43.1% | 1,394 / 3,236 |
| Ducted and non-ducted | 70% | 1,303 / 1,862 |
Manufacturers with the most qualifying models
Among manufacturers with at least 5 models.
| Manufacturer | Qualifying | Share of its models |
|---|---|---|
| Gree | 223 of 395 | 56.5% |
| Mitsubishi Electric | 200 of 373 | 53.6% |
| Midea | 180 of 402 | 44.8% |
| Lennox | 121 of 371 | 32.6% |
| Carrier | 120 of 701 | 17.1% |
| Rheem | 102 of 291 | 35.1% |
| Hisense | 94 of 159 | 59.1% |
| Trane | 68 of 309 | 22% |
| Fujitsu | 56 of 164 | 34.1% |
| Daikin | 55 of 367 | 15% |
Qualifying models
Sorted by manufacturer and model. Use Explore for other sorts and filters.
| # · Outdoor model | Manufacturer | Size · type | COP@5°F | Cap. 5/47 | HSPF2 | SEER2 | Meets | Combos | AHRI ref. |
|---|---|---|---|---|---|---|---|---|---|
| 1901A-KMH36QV-1AKerr · A-KMH Series | KERR | 3 tons36,000 Btu/h · Ducted and non-ducted and mixed (multi-zone) | 2.00 | 103% | 10.9 | 22.4 | CEE 25CEE 26XcelES CC | 3 | 217169740 |
| 1902A-KMH48PV-1KERR · A series | KERR | 4 tons48,000 Btu/h · Ducted and non-ducted and mixed (multi-zone) | 2.00 | 92% | 9.8 | 21.8 | CEE 25CEE 26XcelES CC | 3 | 207657606 |
| 1903A-KMH55PV-1KERR · A-series | KERR | 4.5 tons55,000 Btu/h · Ducted and non-ducted and mixed (multi-zone) | 1.77 | 85% | 9.5 | 22.0 | CEE 25CEE 26XcelES CC | 3 | 214232458 |
| 1904KMIR218-H221-2KLIMAIRE | KLIMAIRE | 1.5 tons18,000 Btu/h · Ducted and non-ducted and mixed (multi-zone) | 2.00 | 66% | 10.2 | 21.0 | CEE 25CEE 26Xcel | 3 | 209862181 |
| 1905KMIR324-H217-2KLIMAIRE | KLIMAIRE | 2 tons24,000 Btu/h · Ducted and non-ducted and mixed (multi-zone) | 1.90 | 75% | 9.7 | 21.3 | CEE 25CEE 26Xcel | 3 | 209862185 |
| 1906KMIR327-H217-2KLIMAIRE | KLIMAIRE | 2.5 tons27,000 Btu/h · Ducted and non-ducted and mixed (multi-zone) | 1.83 | 71% | 9.2 | 23.5 | CEE 25CEE 26Xcel | 3 | 209862187 |
| 1907KOIF24H2-1SKLIMAIREwith ducted air handler KIDF24H2-1S | KLIMAIRE | 2 tons24,000 Btu/h · Ducted | 1.91 | 94% | 10.0 | 17.4 | CEE 25CEE 26Xcel | 1 | 212316040 |
| 1908KOIF30H2-1SKLIMAIREwith ducted air handler KIDF30H2-1S | KLIMAIRE | 2.5 tons30,000 Btu/h · Ducted | 1.80 | 73% | 8.9 | 16.2 | CEE 25CEE 26Xcel | 1 | 212316041 |
| 1909KOIF36H2-1SKLIMAIREwith ducted air handler KIDF36H2-1S | KLIMAIRE | 3 tons36,000 Btu/h · Ducted | 1.97 | 86% | 9.5 | 16.0 | CEE 25CEE 26Xcel | 1 | 212316042 |
| 1910KOIQ12H1-4Klimairewith ductless indoor unit KIWQ12H1-4T | KLIMAIRE | 1 ton12,000 Btu/h · Non-ducted | 1.80 | 70% | 8.5 | 19.0 | CEE 25CEE 26Xcel | 1 | 213244560 |
| 1911KOIQ12H2-4Klimairewith ductless indoor unit KIWQ12H2-4T | KLIMAIRE | 1 ton12,000 Btu/h · Non-ducted | 1.80 | 70% | 8.5 | 19.0 | CEE 25CEE 26Xcel | 1 | 213244561 |
| 1912KOIU09H1-1Klimairewith ductless indoor unit KIWU09H1-1A | KLIMAIRE | 1 ton9,000 Btu/h · Non-ducted | 1.80 | 74% | 9.0 | 23.0 | CEE 25CEE 26Xcel | 1 | 213244565 |
| 1913KOIU09H2-1Klimairewith ductless indoor unit KIWU09H2-1A | KLIMAIRE | 1 ton9,000 Btu/h · Non-ducted | 1.80 | 77% | 9.2 | 23.5 | CEE 25CEE 26Xcel | 1 | 213244566 |
| 1914KOIU12H1-1Klimairewith ductless indoor unit KIWU12H1-1A | KLIMAIRE | 1 ton12,000 Btu/h · Non-ducted | 1.80 | 73% | 9.0 | 22.0 | CEE 25CEE 26Xcel | 1 | 213244567 |
| 1915KOIU12H2-1Klimairewith ductless indoor unit KIWU12H2-1A | KLIMAIRE | 1 ton12,000 Btu/h · Non-ducted | 1.80 | 76% | 9.5 | 23.0 | CEE 25CEE 26Xcel | 1 | 213244568 |
| 1916KSIE009-H221-O-2KLIMAIREwith ductless indoor unit KSIE009-H221-IW-2 | KLIMAIRE | 1 ton9,000 Btu/h · Ducted and non-ducted | 2.11 | 80% | 11.4 | 24.0 | CEE 25CEE 26Xcel | 3 | 209862149 |
| 1917KSIE012-H220-O-2KLIMAIREwith ductless indoor unit KTIR12-H2 | KLIMAIRE | 1 ton12,000 Btu/h · Ducted and non-ducted | 2.28 | 67% | 10.0 | 22.7 | CEE 25CEE 26Xcel | 3 | 209862158 |
| 1918KSIE018-H220-O-2KLIMAIREwith ducted air handler KDIP18-H2 | KLIMAIRE | 1.5 tons17,000 Btu/h · Ducted and non-ducted | 2.40 | 65% | 10.6 | 20.0 | CEE 25CEE 26Xcel | 4 | 209862162 |
| 1919KSIE024-H220-O-2KLIMAIREwith ducted air handler KDIP24-H2 | KLIMAIRE | 2 tons23,000 Btu/h · Ducted and non-ducted | 2.30 | 80% | 11.2 | 19.0 | CEE 25CEE 26Xcel | 4 | 209862163 |
| 1920KSIH009-H225-O-2KLIMAIREwith ductless indoor unit KSIH009-H225-IW-2 | KLIMAIRE | 1 ton9,000 Btu/h · Ducted and non-ducted | 1.90 | 94% | 11.6 | 26.4 | CEE 25CEE 26Xcel | 3 | 209862153 |
| 1921KSIH012-H222-O-2KLIMAIREwith ducted air handler KDIP12-H2 | KLIMAIRE | 1 ton12,000 Btu/h · Ducted and non-ducted | 1.96 | 97% | 10.0 | 19.5 | CEE 25CEE 26Xcel | 3 | 209862171 |
| 1922KSIH018-H220-O-2KLIMAIREwith ductless indoor unit KSIH018-H220-IW-2 | KLIMAIRE | 1.5 tons18,000 Btu/h · Ducted and non-ducted | 1.89 | 96% | 10.6 | 22.0 | CEE 25CEE 26Xcel | 4 | 209862155 |
| 1923KSIH024-H220-O-2KLIMAIREwith ductless indoor unit KUIR24-H2 | KLIMAIRE | 2 tons24,000 Btu/h · Ducted and non-ducted | 2.10 | 100% | 11.0 | 20.5 | CEE 25CEE 26CEE AdvXcelDOE | 4 | 209862174 |
| 1924KSIR048-H218-2KLIMAIREwith ductless indoor unit KTIS48-H2 | KLIMAIRE | 4 tons48,000 Btu/h · Ducted and non-ducted | 1.98 | 69% | 9.8 | 18.5 | Xcel | 3 | 212316047 |
| 1925LBH12AWOLBG Productswith ductless indoor unit LBH12AWI | LBG Products | 1 ton12,100 Btu/h · Non-ducted | 1.84 | 74% | 9.0 | 25.0 | CEE 25CEE 26Xcel | 1 | 206726729 |