Two ways to read the same certified data. Switch any time; your choice is remembered on this device.
ADP vs EMI heat pumps
Measured against models of the same size and duct type, EMI scores higher on 4 of the 6 ratings. ADP has 15 outdoor models, EMI has 15 outdoor models. ADP and EMI have no QMID on file and are not ranked.
New to heat pump ratings? The Simple view explains them in plain words →
CompareData as of updated · sources
Against comparable models
Each cell is the share of same-size, same-type models that the manufacturer’s typical model beats (50% is typical); the higher score is in bold. Raw medians are underneath for context: they depend on which sizes each one makes, so they are not compared.
- ADP
- EMI
- Other ranked manufacturers
Source: AHRI Directory, NEEP · as of
| Rating | ADP | EMI |
|---|---|---|
| Efficiency index | 49%median — | 62%median — |
| COP at 5°F | 35%median 1.86 | 56%median 2.00 |
| Capacity retention at 5°F | 86% (higher)median 96% | 63% (higher)median 95% |
| HSPF2 | 51%median 8.5 | 69%median 10.5 |
| SEER2 | 37%median 15.2 | 61%median 21.4 |
| EER2 | 43%median 11.0 | 60%median 12.5 |
| Heating capacity at 5°F | 84% (higher)median 33,000 Btu/h | 60% (higher)median 18,000 Btu/h |
| Outdoor models | 15 | 15 |
| AHRI certifications | 259 | 27 |
Share of models meeting each standard
| Standard | ADP | EMI |
|---|---|---|
| CEE 2025 Tier 1 (Split ASHP) | 26.7%4 models | 86.7%13 models |
| CEE 2026 Tier 1 (Split ASHP) | 26.7%4 models | 86.7%13 models |
| CEE Advanced Tier (Split ASHP) | 6.7%1 models | 6.7%1 models |
| Xcel Energy Colorado cold-climate ASHP (2025) | 86.7%13 models | 73.3%11 models |
| DOE Cold Climate Heat Pump Challenge | 6.7%1 models | 6.7%1 models |
| ENERGY STAR Cold Climate | 0%0 models | 73.3%11 models |
Sizes and duct types offered
Models in each peer group, with the efficiency index of those models against the rest of the group.
- ADP
- EMI
- All models of the group
Raw ratings are only placed side by side within one size and duct type, where they are comparable.
Source: AHRI Directory · as of
| Size and duct type | ADP | EMI |
|---|---|---|
| Ducted, up to 1.5 tons | 3 · index 45% | 1 · index 77% |
| Ducted, 2 tons | 4 · index 44% | None |
| Ducted, 2.5–3 tons | 3 · index 43% | 2 · index 81% |
| Ducted, 3.5–4.5 tons | 5 · index 58% | 1 · index 84% |
| Non-ducted, up to 1.5 tons | None | 8 · index 60% |
| Non-ducted, 2 tons | None | 2 · index 53% |
| Non-ducted, 2.5–3 tons | None | 4 · index 46% |
| Non-ducted, 3.5–4.5 tons | None | 1 · index 76% |
Cold-climate and all-around picks, size class by size class
Each manufacturer’s best model on each board in every size and duct type, side by side; the higher score is in bold. Both scores are 0–100 against every model of that size class (the line on each bar is 50, the typical model there), so the two compare fairly even when they make different sizes.
Cold-climate picks
| Size and duct type | ADPCold-climate score, best model | EMICold-climate score, best model |
|---|---|---|
| Ducted, up to 1.5 tons | 57.1(50 is the typical model of its size class)KUSXA181Awith ducted air handler V36H***P12*+TXV+TD2 of 2 models qualify · AHRI 217350899 | 70.8(50 is the typical model of its size class) (higher)EMXMZ218DA1 of 1 models qualify · AHRI 215444941 |
| Ducted, 2 tons | 68.4(50 is the typical model of its size class)KUSXB241Awith ducted air handler FE*G32*30+TXV5 of 5 models qualify · AHRI 217730117 | No models in this size class |
| Ducted, 2.5–3 tons | 54.9(50 is the typical model of its size class)KUSXB361Awith ducted air handler FC*G32*36+TXV+TD3 of 3 models qualify · AHRI 217730111 | 82.5(50 is the typical model of its size class) (higher)EMXMZ436DA2 of 2 models qualify · AHRI 215444947 |
| Ducted, 3.5–4.5 tons | 66.4(50 is the typical model of its size class)KUSXA482Awith ducted air handler HG48*60+TXV+TD5 of 5 models qualify · AHRI 217198710 | 82.7(50 is the typical model of its size class) (higher)EMXMZ548DA1 of 1 models qualify · AHRI 215444950 |
| Non-ducted, up to 1.5 tons | No models in this size class | 96.7(50 is the typical model of its size class)EMXSZ106DAwith ductless indoor unit EMXWAL06DA6 of 8 models qualify · AHRI 215444935 |
| Non-ducted, 2 tons | No models in this size class | 88.4(50 is the typical model of its size class)EMXSZ124DAwith ductless indoor unit EMXWAL24DA2 of 2 models qualify · AHRI 215444939 |
| Non-ducted, 2.5–3 tons | No models in this size class | 78.0(50 is the typical model of its size class)EMXMZ436DA2 of 4 models qualify · AHRI 215444948 |
| Non-ducted, 3.5–4.5 tons | No models in this size class | 73.4(50 is the typical model of its size class)EMXMZ548DA1 of 1 models qualify · AHRI 215444951 |
All-around best
| Size and duct type | ADPAll-around score, best model | EMIAll-around score, best model |
|---|---|---|
| Ducted, up to 1.5 tons | 44.7(50 is the typical model of its size class)KUSXA181Awith ducted air handler V36H***P12*+TXV+TD2 of 2 models have all five ratings · AHRI 217350899 | 77.4(50 is the typical model of its size class) (higher)EMXMZ218DA1 of 1 models have all five ratings · AHRI 215444941 |
| Ducted, 2 tons | 53.2(50 is the typical model of its size class)KUSXB241Awith ducted air handler FE*G32*30+TXV4 of 4 models have all five ratings · AHRI 217730117 | No models in this size class |
| Ducted, 2.5–3 tons | 53.4(50 is the typical model of its size class)KUSXA361Awith ducted air handler V36H175P15*+TXV+TD4 of 4 models have all five ratings · AHRI 217350909 | 83.6(50 is the typical model of its size class) (higher)EMXMZ436DA2 of 2 models have all five ratings · AHRI 215444947 |
| Ducted, 3.5–4.5 tons | 65.1(50 is the typical model of its size class)KUSXA422Awith ducted air handler HG48*60+TXV+TD5 of 5 models have all five ratings · AHRI 217198708 | 83.9(50 is the typical model of its size class) (higher)EMXMZ548DA1 of 1 models have all five ratings · AHRI 215444950 |
| Non-ducted, up to 1.5 tons | No models in this size class | 96.2(50 is the typical model of its size class)EMXSZ106DAwith ductless indoor unit EMXWAL06DA8 of 8 models have all five ratings · AHRI 215444935 |
| Non-ducted, 2 tons | No models in this size class | 76.4(50 is the typical model of its size class)EMXSZ124DAwith ductless indoor unit EMXWAL24DA2 of 2 models have all five ratings · AHRI 215444939 |
| Non-ducted, 2.5–3 tons | No models in this size class | 78.3(50 is the typical model of its size class)EMXMZ436DA4 of 4 models have all five ratings · AHRI 215444946 |
| Non-ducted, 3.5–4.5 tons | No models in this size class | 75.6(50 is the typical model of its size class)EMXMZ548DA1 of 1 models have all five ratings · AHRI 215444949 |
Standout model on each rating
Each manufacturer’s model that beats the largest share of comparable models on the rating; the higher share is in bold.
| Rating | ADP | EMI |
|---|---|---|
| COP at 5°F | beats 77% · 2.12KUSXB241ADucted, up to 1.5 tons | beats 97% · 2.40EMXSZ106DANon-ducted, up to 1.5 tons |
| Capacity retention at 5°F | beats 100% · 128%KUSXA301ADucted, 2 tons | beats 94% · 110%EMXSZ106DANon-ducted, up to 1.5 tons |
| HSPF2 | beats 73% · 9.1KUSXA482ADucted, 3.5–4.5 tons | beats 99% · 14.8EMXSZ106DANon-ducted, up to 1.5 tons |
| SEER2 | beats 50% · 16.0KUSXA422ADucted, 3.5–4.5 tons | beats 96% · 20.4EMXMZ548DADucted, 3.5–4.5 tons |
| EER2 | beats 67% · 11.7KUSXA422ADucted, 3.5–4.5 tons | beats 99% · 18.0EMXSZ106DANon-ducted, up to 1.5 tons |
| Heating capacity at 5°F | beats 100% · 24,000 Btu/hKUSXB241ADucted, up to 1.5 tons | beats 97% · 19,000 Btu/hEMXMZ218DANon-ducted, up to 1.5 tons |