CEE 2025 Tier 1 (Split ASHP): 7,036 qualifying heat pumps

The CEE 2025 Tier 1 efficiency level for split air-source heat pumps, used by many utility rebate programs.

New to heat pump ratings? The Simple view explains them in plain words →

Consortium for Energy EfficiencyData as of updated · sources

Share of models
57.1%
Qualifying models
7,036
Qualifying certifications
220,949
Paths
2

Criteria

A model qualifies when one certification meets every value in at least one row.
PathSEER2EER2HSPF2COP@5°FCap. 5/47
Path A (heating-dominated)≥ 16≥ 9.8≥ 8.5≥ 1.75≥ 60%
Path B (cooling-dominated / dual fuel)≥ 16≥ 11≥ 8≥ 1.75≥ 45%

Source: Consortium for Energy Efficiency

Where the thresholds fall

Every model's representative certification on each rating CEE 2025 checks, with its thresholds drawn. A model must clear every line of one path at once, on one certification, so these single-rating views show each hurdle, not the combined pass rate.
COP at 5°F11,219 rated models · median 2.00At least 84% of rated models reach 1.75 on this rating alone.
+40 above12 below

Show the data as a table
Models per COP at 5°F range
COP@5°F rangeModels
Below 1.4012
1.40 to under 1.5079
1.50 to under 1.60176
1.60 to under 1.70335
1.70 to under 1.801,180
1.80 to under 1.902,238
1.90 to under 2.001,350
2.00 to under 2.102,426
2.10 to under 2.201,325
2.20 to under 2.30778
2.30 to under 2.40511
2.40 to under 2.50260
2.50 to under 2.60215
2.60 to under 2.70132
2.70 to under 2.8080
2.80 to under 2.9051
2.90 to under 3.0031
3.00 and above40
Baseline: median2.00
Baseline: CEE 2025 1.751.75

Source: AHRI Directory · as of

Capacity retention at 5°F11,154 rated models · median 72%92% of rated models reach 45% (the lowest path) on this rating alone.
+40 above51 below

Show the data as a table
Models per Capacity retention at 5°F range
Cap. 5/47 rangeModels
Below 30%51
30 to under 35%28
35 to under 40%337
40 to under 45%467
45 to under 50%519
50 to under 55%566
55 to under 60%526
60 to under 65%684
65 to under 70%763
70 to under 75%2,401
75 to under 80%1,156
80 to under 85%798
85 to under 90%375
90 to under 95%720
95 to under 100%580
100 to under 105%757
105 to under 110%151
110 to under 115%148
115 to under 120%27
120 to under 125%41
125 to under 130%19
130% and above40
Baseline: median72%
Baseline: Path B 45%45%
Baseline: Path A 60%60%

Source: AHRI Directory · as of

HSPF212,304 rated models · median 9.075% of rated models reach 8 (the lowest path) on this rating alone.
+62 above41 below

Show the data as a table
Models per HSPF2 range
HSPF2 rangeModels
Below 6.541
6.5 to under 6.8983
6.8 to under 7.064
7.0 to under 7.3528
7.3 to under 7.515
7.5 to under 7.81,111
7.8 to under 8.0382
8.0 to under 8.3722
8.3 to under 8.5178
8.5 to under 8.81,451
8.8 to under 9.0196
9.0 to under 9.31,501
9.3 to under 9.5132
9.5 to under 9.81,370
9.8 to under 10.0306
10.0 to under 10.31,626
10.3 to under 10.5228
10.5 to under 10.8602
10.8 to under 11.080
11.0 to under 11.3294
11.3 to under 11.559
11.5 to under 11.8122
11.8 to under 12.021
12.0 to under 12.327
12.3 to under 12.52
12.5 to under 12.892
12.8 to under 13.00
13.0 to under 13.323
13.3 to under 13.59
13.5 to under 13.843
13.8 to under 14.034
14.0 and above62
Baseline: median9.0
Baseline: Path B 88.0
Baseline: Path A 8.58.5

Source: AHRI Directory · as of

SEER212,328 rated models · median 18.068% of rated models reach 16 on this rating alone.
+54 above54 below

Show the data as a table
Models per SEER2 range
SEER2 rangeModels
Below 12.554
12.5 to under 13.014
13.0 to under 13.5900
13.5 to under 14.0338
14.0 to under 14.51,002
14.5 to under 15.0192
15.0 to under 15.51,102
15.5 to under 16.0283
16.0 to under 16.5624
16.5 to under 17.0188
17.0 to under 17.5849
17.5 to under 18.0214
18.0 to under 18.5680
18.5 to under 19.0393
19.0 to under 19.5745
19.5 to under 20.0182
20.0 to under 20.5918
20.5 to under 21.0161
21.0 to under 21.5783
21.5 to under 22.0162
22.0 to under 22.5508
22.5 to under 23.0197
23.0 to under 23.5661
23.5 to under 24.0111
24.0 to under 24.5294
24.5 to under 25.0151
25.0 to under 25.5286
25.5 to under 26.075
26.0 to under 26.539
26.5 to under 27.018
27.0 to under 27.560
27.5 to under 28.022
28.0 to under 28.57
28.5 to under 29.01
29.0 to under 29.515
29.5 to under 30.022
30.0 to under 30.523
30.5 and above54
Baseline: median18.0
Baseline: CEE 2025 1616.0

Source: AHRI Directory · as of

EER212,324 rated models · median 11.5At least 85% of rated models reach 9.8 (the lowest path) on this rating alone.
+31 above2 below

Show the data as a table
Models per EER2 range
EER2 rangeModels
Below 8.02
8.0 to under 8.595
8.5 to under 9.0214
9.0 to under 9.5702
9.5 to under 10.0831
10.0 to under 10.5881
10.5 to under 11.01,359
11.0 to under 11.51,678
11.5 to under 12.01,904
12.0 to under 12.51,870
12.5 to under 13.0950
13.0 to under 13.5914
13.5 to under 14.0232
14.0 to under 14.5274
14.5 to under 15.0114
15.0 to under 15.5179
15.5 to under 16.05
16.0 to under 16.531
16.5 to under 17.023
17.0 to under 17.535
17.5 and above31
Baseline: median11.5
Baseline: Path A 9.89.8
Baseline: Path B 1111.0

Source: AHRI Directory · as of

Qualification by size

Share of models meeting CEE 2025, by size
Show the data as a table
Share of models meeting CEE 2025, by size
GroupQualifying share
Up to 1.5 tons62.1% · 2,928 of 4,715
2 tons67.6% · 1,181 of 1,748
2.5–3 tons57.3% · 1,560 of 2,724
3.5–4.5 tons45.5% · 1,222 of 2,687
5 tons and up31.7% · 145 of 458

Qualification by duct type

Models certified only with ducted, only with non-ducted, or with both kinds of indoor unit
TypeShareQualifying / total
Ducted34.5%2,089 / 6,056
Non-ducted69%2,820 / 4,087
Ducted and non-ducted97.2%2,127 / 2,189

Manufacturers with the most qualifying models

Among manufacturers with at least 5 models.
Qualifying models and share of each manufacturer’s catalog
ManufacturerQualifyingShare of its models
Gree580 of 71780.9%
Midea412 of 54675.5%
Carrier328 of 81640.2%
Daikin150 of 39438.1%
Lennox147 of 33743.6%
BlueRidge145 of 19275.5%
Trane140 of 36338.6%
TCL134 of 17775.7%
Hisense129 of 16180.1%
Mitsubishi Electric126 of 15680.8%

Qualifying models

Sorted by manufacturer and model. Use Explore for other sorts and filters.
Models meeting CEE 2025 Tier 1 (Split ASHP), page 255 of 282
# · Outdoor modelManufacturerSize · typeCOP@5°FCap. 5/47HSPF2SEER2MeetsCombosAHRI ref.
63515TWX5048A1TRANEwith ducted air handler DH60T4JTrane4 tons45,000 Btu/h · Ducted2.7566%7.815.5CEE 25CEE 26791216952428
63525TWX6024A1TRANE · 16 Single-Stage Heat Pump with WeatherGuard Topwith ducted air handler 5TEM6D06AV41+TDR+TSTATTrane2 tons24,800 Btu/h · Ducted2.2650%8.116.0CEE 25CEE 2684218395970
63535TWX6030A1TRANE · 16 Single-Stage Heat Pump with WeatherGuard Topwith indoor coil 5PX*B006AS3+TSTAT and furnace *UHMB080CCV3Trane2.5 tons28,400 Btu/h · Ducted2.1951%8.016.0CEE 25CEE 26170218396009
63545TWX6036A1TRANE · 16 Single-Stage Heat Pump with WeatherGuard Topwith indoor coil 5PX*C007AS3+TSTAT and furnace S8V2C100M5PDBTrane3 tons34,400 Btu/h · Ducted2.3755%8.116.0CEE 25CEE 26136218396147
63555TWX6042A1TRANE · 16 Single-Stage Heat Pump with WeatherGuard Topwith ducted air handler 5TEMCD07BV51+TDR+TSTATTrane3.5 tons41,000 Btu/h · Ducted2.2948%8.116.0CEE 2577218788189
63565TWX6048A1TRANE · 16 Single-Stage Heat Pump with WeatherGuard Topwith ducted air handler 5TEMCD07BV51+TDR+TSTATTrane4 tons46,500 Btu/h · Ducted2.2652%8.116.0CEE 25CEE 2662218788190
63575TWX7024A1TRANEwith ducted air handler L(E,G)M36CJTrane2 tons21,800 Btu/h · Ducted2.4670%8.116.0CEE 25CEE 26XcelES CC546218350179
63585TWX7036A1TRANEwith indoor coil DH60T4J and furnace L8V1A040U3VSBTrane2.5 tons32,200 Btu/h · Ducted2.2965%8.517.0CEE 25CEE 26XcelES CC1,024217208633
63595TWX7048A1TRANEwith indoor coil DH60T4J and furnace S8X1D120M5PSCTrane3.5 tons43,000 Btu/h · Ducted2.3267%9.017.5CEE 25CEE 26XcelES CC453217209013
63605TWX7060A1TRANEwith indoor coil DH60T4J and furnace S8V2D120M5PCBTrane4.5 tons51,000 Btu/h · Ducted2.3267%8.515.5CEE 25CEE 26XcelES CC276217209080
6361A5HL5024A1RUNTRUwith ducted air handler L(E,F)W36DJTrane2 tons21,200 Btu/h · Ducted2.0386%7.815.2CEE 25CEE 26XcelES CC189217221781
6362A5HL5024A1000AARUNTRU · A5HL5with ducted air handler A5AHV002A1B3Trane2 tons23,000 Btu/h · Ducted1.7578%8.116.0CEE 25CEE 26XcelES CC8216439103
6363A5HL5036A1RUNTRUwith ducted air handler CM36B4J+TDRTrane2.5 tons28,400 Btu/h · Ducted1.97109%8.114.3CEE 25CEE 26XcelES CC163218034123
6364A5HL5036A1000AARUNTRU · A5HL5with ducted air handler A5AHV004A1D3Trane3 tons34,000 Btu/h · Ducted1.7579%8.116.0CEE 25CEE 26XcelES CC8216439104
6365A5HL5048A1AMERISTAR · A5HL5with indoor coil 5TXCB006AS3 and furnace A952V060BU4SBTrane3.5 tons41,000 Btu/h · Ducted1.8080%8.115.2CEE 25CEE 26XcelES CC170217162406
6366A5HL5048A1000AARUNTRU · A5HL5with ducted air handler A5AHV006A1D3Trane4 tons46,000 Btu/h · Ducted1.7579%8.116.0CEE 25CEE 26XcelES CC8216439106
6367A5HP5018A1RUNTRUwith indoor coil D(A,C,E)30A3J+TDR and furnace A952V060BU4SATrane1.5 tons16,600 Btu/h · Ducted2.4465%7.815.2CEE 25405217083379
6368A5HP5024A1AMERISTARwith indoor coil D(A,C,E)36C3J+TDR and furnace A951X060BU4SATrane2 tons21,600 Btu/h · Ducted2.7968%8.515.2CEE 25CEE 261,012217084183
6369A5HP5030A1RUNTRUwith indoor coil D(A,C,E)36C3J+TDR and furnace A801X080CM5SDTrane2 tons26,200 Btu/h · Ducted2.7768%7.814.8CEE 25CEE 26841217083538
6370A5HP5036A1RUNTRUwith indoor coil D(A,C,E)36C3J+TDR and furnace A801X080CM5SDTrane2.5 tons31,200 Btu/h · Ducted3.0071%8.515.2CEE 25CEE 26Xcel1,032217083701
6371A5HP5042A1RUNTRUwith indoor coil D(A,C,E)48C3J+TDR and furnace A801X080BM4TDTrane3 tons36,600 Btu/h · Ducted2.7964%8.115.5CEE 25CEE 261,512217083968
6372A5HP5048A1RUNTRUwith ducted air handler DM60B4J+TDRTrane3.5 tons42,000 Btu/h · Ducted2.6965%7.815.2CEE 25CEE 26812216619453
6373M3THS2209A91NARunTru · CXVwith ductless indoor unit M3MHW2209A9N0ATrane1 ton9,000 Btu/h · Non-ducted1.7576%9.523.5CEE 25CEE 26Xcel2212586155
6374M3THS2212A91NARunTru · CXVwith ductless indoor unit M3MHW2212A9N0ATrane1 ton12,000 Btu/h · Non-ducted1.7575%9.523.0CEE 25CEE 26Xcel2212586156
6375M5THM2318A12NA*RunTru · 23U MultiTrane1.5 tons18,000 Btu/h · Non-ducted2.0080%10.524.0CEE 25CEE 26XcelES CC2218067082

Explore qualifying models by COP at 5°F