CEE 2026 Tier 1 (Split ASHP): 6,854 qualifying heat pumps
The 2026 revision of CEE Tier 1, with higher low-temperature capacity requirements than 2025.
New to heat pump ratings? The Simple view explains them in plain words →
Consortium for Energy EfficiencyData as of updated · sources
- Share of models
- 55.6%
- Qualifying models
- 6,854
- Qualifying certifications
- 202,824
- Paths
- 2
Criteria
| Path | SEER2 | EER2 | HSPF2 | COP@5°F | Cap. 5/47 |
|---|---|---|---|---|---|
| Path A (heating-dominated) | ≥ 16 | ≥ 9.8 | ≥ 8.5 | ≥ 1.75 | ≥ 65% |
| Path B (cooling-dominated / dual fuel) | ≥ 16 | ≥ 11 | ≥ 8 | ≥ 1.75 | ≥ 50% |
Source: Consortium for Energy Efficiency
Where the thresholds fall
Every model's representative certification on each rating CEE 2026 checks, with its thresholds drawn. A model must clear every line of one path at once, on one certification, so these single-rating views show each hurdle, not the combined pass rate.
Show the data as a table
| COP@5°F range | Models |
|---|---|
| Below 1.40 | 12 |
| 1.40 to under 1.50 | 79 |
| 1.50 to under 1.60 | 176 |
| 1.60 to under 1.70 | 335 |
| 1.70 to under 1.80 | 1,180 |
| 1.80 to under 1.90 | 2,238 |
| 1.90 to under 2.00 | 1,351 |
| 2.00 to under 2.10 | 2,428 |
| 2.10 to under 2.20 | 1,325 |
| 2.20 to under 2.30 | 777 |
| 2.30 to under 2.40 | 512 |
| 2.40 to under 2.50 | 260 |
| 2.50 to under 2.60 | 215 |
| 2.60 to under 2.70 | 132 |
| 2.70 to under 2.80 | 80 |
| 2.80 to under 2.90 | 51 |
| 2.90 to under 3.00 | 31 |
| 3.00 and above | 40 |
| Baseline: median | 2.00 |
| Baseline: CEE 2026 1.75 | 1.75 |
Source: AHRI Directory · as of
Show the data as a table
| Cap. 5/47 range | Models |
|---|---|
| Below 30% | 51 |
| 30 to under 35% | 28 |
| 35 to under 40% | 337 |
| 40 to under 45% | 467 |
| 45 to under 50% | 519 |
| 50 to under 55% | 566 |
| 55 to under 60% | 526 |
| 60 to under 65% | 684 |
| 65 to under 70% | 763 |
| 70 to under 75% | 2,400 |
| 75 to under 80% | 1,156 |
| 80 to under 85% | 799 |
| 85 to under 90% | 375 |
| 90 to under 95% | 720 |
| 95 to under 100% | 582 |
| 100 to under 105% | 758 |
| 105 to under 110% | 151 |
| 110 to under 115% | 148 |
| 115 to under 120% | 27 |
| 120 to under 125% | 41 |
| 125 to under 130% | 19 |
| 130% and above | 40 |
| Baseline: median | 72% |
| Baseline: Path B 50% | 50% |
| Baseline: Path A 65% | 65% |
Source: AHRI Directory · as of
Show the data as a table
| HSPF2 range | Models |
|---|---|
| Below 6.5 | 41 |
| 6.5 to under 6.8 | 983 |
| 6.8 to under 7.0 | 64 |
| 7.0 to under 7.3 | 528 |
| 7.3 to under 7.5 | 15 |
| 7.5 to under 7.8 | 1,112 |
| 7.8 to under 8.0 | 381 |
| 8.0 to under 8.3 | 724 |
| 8.3 to under 8.5 | 177 |
| 8.5 to under 8.8 | 1,450 |
| 8.8 to under 9.0 | 196 |
| 9.0 to under 9.3 | 1,500 |
| 9.3 to under 9.5 | 132 |
| 9.5 to under 9.8 | 1,372 |
| 9.8 to under 10.0 | 306 |
| 10.0 to under 10.3 | 1,627 |
| 10.3 to under 10.5 | 228 |
| 10.5 to under 10.8 | 603 |
| 10.8 to under 11.0 | 80 |
| 11.0 to under 11.3 | 294 |
| 11.3 to under 11.5 | 59 |
| 11.5 to under 11.8 | 122 |
| 11.8 to under 12.0 | 21 |
| 12.0 to under 12.3 | 27 |
| 12.3 to under 12.5 | 2 |
| 12.5 to under 12.8 | 92 |
| 12.8 to under 13.0 | 0 |
| 13.0 to under 13.3 | 23 |
| 13.3 to under 13.5 | 9 |
| 13.5 to under 13.8 | 43 |
| 13.8 to under 14.0 | 34 |
| 14.0 and above | 62 |
| Baseline: median | 9.0 |
| Baseline: Path B 8 | 8.0 |
| Baseline: Path A 8.5 | 8.5 |
Source: AHRI Directory · as of
Show the data as a table
| SEER2 range | Models |
|---|---|
| Below 12.5 | 54 |
| 12.5 to under 13.0 | 14 |
| 13.0 to under 13.5 | 900 |
| 13.5 to under 14.0 | 338 |
| 14.0 to under 14.5 | 1,004 |
| 14.5 to under 15.0 | 192 |
| 15.0 to under 15.5 | 1,100 |
| 15.5 to under 16.0 | 284 |
| 16.0 to under 16.5 | 624 |
| 16.5 to under 17.0 | 188 |
| 17.0 to under 17.5 | 848 |
| 17.5 to under 18.0 | 214 |
| 18.0 to under 18.5 | 681 |
| 18.5 to under 19.0 | 393 |
| 19.0 to under 19.5 | 745 |
| 19.5 to under 20.0 | 182 |
| 20.0 to under 20.5 | 917 |
| 20.5 to under 21.0 | 162 |
| 21.0 to under 21.5 | 783 |
| 21.5 to under 22.0 | 162 |
| 22.0 to under 22.5 | 508 |
| 22.5 to under 23.0 | 197 |
| 23.0 to under 23.5 | 661 |
| 23.5 to under 24.0 | 111 |
| 24.0 to under 24.5 | 294 |
| 24.5 to under 25.0 | 151 |
| 25.0 to under 25.5 | 286 |
| 25.5 to under 26.0 | 75 |
| 26.0 to under 26.5 | 39 |
| 26.5 to under 27.0 | 19 |
| 27.0 to under 27.5 | 61 |
| 27.5 to under 28.0 | 22 |
| 28.0 to under 28.5 | 7 |
| 28.5 to under 29.0 | 1 |
| 29.0 to under 29.5 | 15 |
| 29.5 to under 30.0 | 22 |
| 30.0 to under 30.5 | 23 |
| 30.5 and above | 54 |
| Baseline: median | 18.0 |
| Baseline: CEE 2026 16 | 16.0 |
Source: AHRI Directory · as of
Show the data as a table
| EER2 range | Models |
|---|---|
| Below 8.0 | 2 |
| 8.0 to under 8.5 | 94 |
| 8.5 to under 9.0 | 214 |
| 9.0 to under 9.5 | 703 |
| 9.5 to under 10.0 | 831 |
| 10.0 to under 10.5 | 881 |
| 10.5 to under 11.0 | 1,359 |
| 11.0 to under 11.5 | 1,679 |
| 11.5 to under 12.0 | 1,904 |
| 12.0 to under 12.5 | 1,869 |
| 12.5 to under 13.0 | 951 |
| 13.0 to under 13.5 | 914 |
| 13.5 to under 14.0 | 232 |
| 14.0 to under 14.5 | 275 |
| 14.5 to under 15.0 | 114 |
| 15.0 to under 15.5 | 180 |
| 15.5 to under 16.0 | 5 |
| 16.0 to under 16.5 | 31 |
| 16.5 to under 17.0 | 23 |
| 17.0 to under 17.5 | 35 |
| 17.5 and above | 31 |
| Baseline: median | 11.5 |
| Baseline: Path A 9.8 | 9.8 |
| Baseline: Path B 11 | 11.0 |
Source: AHRI Directory · as of
Qualification by size
- Up to 1.5 tons60.9% · 2,870 of 4,716
- 2 tons66.2% · 1,157 of 1,748
- 2.5–3 tons54.6% · 1,489 of 2,726
- 3.5–4.5 tons44.4% · 1,193 of 2,687
- 5 tons and up31.7% · 145 of 458
Show the data as a table
| Group | Qualifying share |
|---|---|
| Up to 1.5 tons | 60.9% · 2,870 of 4,716 |
| 2 tons | 66.2% · 1,157 of 1,748 |
| 2.5–3 tons | 54.6% · 1,489 of 2,726 |
| 3.5–4.5 tons | 44.4% · 1,193 of 2,687 |
| 5 tons and up | 31.7% · 145 of 458 |
Qualification by duct type
| Type | Share | Qualifying / total |
|---|---|---|
| Ducted | 32.6% | 1,974 / 6,057 |
| Non-ducted | 67.7% | 2,768 / 4,089 |
| Ducted and non-ducted | 96.5% | 2,112 / 2,189 |
Manufacturers with the most qualifying models
Among manufacturers with at least 5 models.
| Manufacturer | Qualifying | Share of its models |
|---|---|---|
| Gree | 572 of 717 | 79.8% |
| Midea | 403 of 546 | 73.8% |
| Carrier | 288 of 816 | 35.3% |
| BlueRidge | 141 of 192 | 73.4% |
| Lennox | 139 of 337 | 41.2% |
| Daikin | 137 of 394 | 34.8% |
| TCL | 134 of 177 | 75.7% |
| Trane | 133 of 363 | 36.6% |
| Mitsubishi Electric | 126 of 156 | 80.8% |
| Hisense | 122 of 161 | 75.8% |
Qualifying models
Sorted by manufacturer and model. Use Explore for other sorts and filters.
| # · Outdoor model | Manufacturer | Size · type | COP@5°F | Cap. 5/47 | HSPF2 | SEER2 | Meets | Combos | AHRI ref. |
|---|---|---|---|---|---|---|---|---|---|
| 2126EDSO-24EECO-AIR · EDS Serieswith ductless indoor unit EDWM-24U | ECO-AIR | 2 tons24,000 Btu/h · Ducted and non-ducted | 2.54 | 78% | 11.7 | 23.0 | CEE 25CEE 26XcelES CC | 3 | 216759939 |
| 2127EDSO-24HECO-AIR · EDS Serieswith ductless indoor unit EDWM-24U | ECO-AIR | 2 tons24,000 Btu/h · Ducted and non-ducted | 2.34 | 83% | 13.5 | 21.0 | CEE 25CEE 26XcelES CC | 3 | 216759983 |
| 2128EDSO-30SECO-AIR · EDS Serieswith ductless indoor unit EDWM-30S | ECO-AIR | 2.5 tons30,000 Btu/h · Non-ducted | 1.94 | 67% | 9.0 | 22.3 | CEE 25CEE 26 | 1 | 216759932 |
| 2129EDSO-33HECO-AIR · EDS Serieswith ductless indoor unit EDWM-33U | ECO-AIR | 3 tons33,000 Btu/h · Non-ducted | 1.98 | 97% | 10.5 | 19.5 | CEE 25CEE 26XcelES CC | 1 | 216759984 |
| 2130EDSO-36HECO-AIR · EDS Serieswith ducted air handler EDHS-36U | ECO-AIR | 3 tons36,000 Btu/h · Ducted and non-ducted | 2.10 | 90% | 11.1 | 17.7 | CEE 25CEE 26XcelES CC | 2 | 216759969 |
| 2131EDSO-48EECO-AIR · EDS Serieswith ductless indoor unit ED4W-48U | ECO-AIR | 4 tons48,000 Btu/h · Ducted and non-ducted | 2.11 | 81% | 9.9 | 19.0 | CEE 25CEE 26XcelES CC | 2 | 216759945 |
| 2132EDSO-48HECO-AIR · EDS Serieswith ducted air handler EDHS-48U | ECO-AIR | 4 tons48,000 Btu/h · Ducted and non-ducted | 2.00 | 91% | 10.8 | 16.7 | CEE 25CEE 26XcelES CC | 2 | 216759970 |
| 2133EDSO-60EECO-AIRwith ducted air handler EDHS-60U | ECO-AIR | 5 tons58,000 Btu/h · Ducted | 2.20 | 67% | 9.7 | 17.0 | CEE 25CEE 26 | 1 | 216759978 |
| 2134EODA17H-2436AD*ECOER · TDi Select 2with ducted air handler EAHDEN-24BE | Ecoer | 2 tons24,000 Btu/h · Ducted | 2.00 | 75% | 8.8 | 18.5 | CEE 25CEE 26XcelES CC | 31 | 218004216 |
| 2135EODA17H-4860AD*ECOER · TDi Select 2with ducted air handler EAHDEN-48BE | Ecoer | 4 tons46,000 Btu/h · Ducted | 2.00 | 71% | 8.8 | 17.5 | CEE 25CEE 26XcelES CC | 34 | 218004219 |
| 2136EODA19H-2436AB*ECOERwith indoor coil D(A,C,E)24C3J+TDR and furnace FG7SA-054C-T23A | Ecoer | 2 tons22,400 Btu/h · Ducted | 2.63 | 93% | 8.5 | 17.0 | CEE 25CEE 26XcelES CC | 94 | 217627902 |
| 2137EODA19H-4860AB*ECOERwith indoor coil D(A,C,E)36C3J+TDR and furnace FG7TC-060D-V24B | Ecoer | 2.5 tons31,000 Btu/h · Ducted | 2.65 | 85% | 9.0 | 18.0 | CEE 25CEE 26XcelES CC | 110 | 217627934 |
| 2138ERDA19H-36AD*ECOER · RTi 2 | Ecoer | 3 tons35,000 Btu/h · Ducted | 1.90 | 70% | 9.2 | 18.3 | CEE 25CEE 26XcelES CC | 1 | 218619224 |
| 2139ERDA19H-60AB*ECOER · RTi 2 | Ecoer | 4.5 tons56,000 Btu/h · Ducted | 1.90 | 71% | 9.5 | 19.0 | CEE 25CEE 26XcelES CC | 1 | 217463590 |
| 2140ERDA19H-60BB*ECOER · RTi 2 | Ecoer | 4.5 tons56,000 Btu/h · Ducted | 1.90 | 71% | 9.3 | 19.0 | CEE 25CEE 26XcelES CC | 1 | 218619223 |
| 2141ESCA16H-24BBAEcoer · SDi Pro 2with ducted air handler EAHDEC-24ABA | Ecoer | 2 tons24,000 Btu/h · Ducted | 1.87 | 83% | 9.7 | 18.1 | CEE 25CEE 26XcelES CC | 1 | 216706027 |
| 2142ESCA16H-36BBAEcoer · SDi Pro 2with ducted air handler ESCT3036BBA | Ecoer | 3 tons36,000 Btu/h · Ducted | 2.00 | 76% | 8.5 | 14.7 | CEE 25CEE 26XcelES CC | 3 | 216706033 |
| 2143ESCA16H-48BBAEcoer · SDi Pro 2with ducted air handler EAHDEC-48ABA | Ecoer | 4 tons48,000 Btu/h · Ducted | 1.85 | 79% | 8.5 | 16.0 | CEE 25CEE 26XcelES CC | 1 | 216706029 |
| 2144ESCA17H-24ABAEcoer · SDi Extreme 2with ducted air handler EAHDEC-24ABA | Ecoer | 2 tons23,000 Btu/h · Ducted | 1.87 | 90% | 10.0 | 18.3 | CEE 25CEE 26XcelES CC | 1 | 216706023 |
| 2145ESCA17H-36ABAEcoer · SDi Extreme 2with ducted air handler ESCT3036BBA | Ecoer | 3 tons36,000 Btu/h · Ducted | 1.90 | 95% | 9.4 | 15.8 | CEE 25CEE 26XcelES CC | 3 | 216706031 |
| 2146ESCA17H-48ABAEcoer · SDi Extreme 2with ducted air handler EAHDEC-48ABA | Ecoer | 4 tons48,000 Btu/h · Ducted | 1.90 | 92% | 9.5 | 16.5 | CEE 25CEE 26XcelES CC | 1 | 216706025 |
| 2147ESCA17H-60ABAEcoer · SDi Extreme 2with ducted air handler ESCT4860CBA | Ecoer | 4.5 tons52,000 Btu/h · Ducted | 1.80 | 80% | 8.5 | 16.0 | CEE 25CEE 26XcelES CC | 3 | 216706032 |
| 2148EOVASIG-MULTI27M3ÉcoNova | ÉcoNova | 2.5 tons27,000 Btu/h · Non-ducted | 2.00 | 71% | 10.5 | 24.0 | CEE 25CEE 26Xcel | 1 | 216767368 |
| 2149EOVASIG-MULTI36M4ÉcoNova | ÉcoNova | 3 tons35,000 Btu/h · Non-ducted | 2.00 | 72% | 10.0 | 22.5 | CEE 25CEE 26Xcel | 1 | 216767369 |
| 2150EOVASIG-MULTI42M5ÉcoNova | ÉcoNova | 3.5 tons42,000 Btu/h · Non-ducted | 2.00 | 71% | 10.0 | 22.0 | CEE 25CEE 26Xcel | 1 | 216767370 |